1.4.6 SUMMARY OF USER FUNCTIONS IN PCSTAR 2 (F2 CONFIGURATION)
The table below provides an overview of all parameters that can be set nt he configuration menu using F2 in PCSTAR2. Default values are in bold type nt he “Input
Range” column.
Function Input Range Description
1.0.0 Operation
1.1.0 Basic parameters
Enter 0 … 60 000 mm or
0 … 197 ft.
1.1.1 Tank height
As per order
The tank height forms the basis for calculating level measurements and for the
relevant current output.
It is defined as the distance between the lower flange surface and the reference
point at the bottom of the tank. The output unit is determined via Fct. 1.2.4.:
Length Unit. The set tank height is the upper limit for Fct. 1.3.4: Scale I1 max
Note: the device will not measure beyond the programmed probe length if the
current output is configured to measure distance or level .
1.1.2 Dead zone Fct.1.5.1
Enter a value
Fct.1.5.1
(Detection delay) … probe length.
Warning:
Critical Parameter
„Minimum measuring distance”
As probe technical data table
The dead zone is the minimum measuring distance from the process connection
(reference point) to the surface of the product. So as not to impair measurement
accuracy, the minimum values given in Section 5.2.3 should be adhered to.
The current output can’t go inside the dead zone.
The output unit is set via Fct. 1.2.4: Length Unit
1 … 100 s. 1.1.3 Time constant
5 s
This function filters possible signal fluctuations when the tank is turbulent.